OPERATING PROCEDURE
17. Removing the thermal protector (TRS))
(1) Remove the service panel. (See Photo 1)
(2) Remove the cover panel front. (See Photo 1)
(3) Pull out the lead wire of high pressure switch and discon-
nect the connector, 63H (yellow) from the multi controller
board in the electrical parts box. (See Photo 11)
(4) Remove the comp felt covering the compressor.
(See Photo 13)
(5) Loosen the clamp or band for the lead wire of the electri-
cal parts box and separator.
(6)
Pull out the thermal protector (TRS) from the holder. (See
Photo 17)
18. Removing the fuse holders
(1) Remove the service panel. (See photo 1)
(2) Remove the fuse covers. (See Figure 4)
(3) Remove 2 screws (3 x 12) for fuse holders to remove the
fuse holders.
(See Figure 4 and Photo 18)
Notes:
1. Bracket, circuit board and other parts can get deformed
when inserting and removing the fuse cover.
2. Remove the fuse cover in the way that surrounding parts
will not be affected.
OCH811A
PHOTOS/FIGURES
Photo 17
Thermal protector
(TRS)
Photo 18
Fuse holders
Figure 4
Fuse covers
153
screws for fuse folders (3×12)