Mitsubishi Electric PUMY-P36NKMU4 Technical & Service Manual page 167

Hide thumbs Also See for PUMY-P36NKMU4:
Table of Contents

Advertisement

OPERATION PROCEDURE
17. Changing the fusible plug
See the following descriptions.
• Be careful not to expose the fusible plug to the braze torch
flame or transfer heat to it. (See Photo 18)
• The temperature of the fusible plug must not become 140°F
(60°C) or more while working. Protect the fusible plug with a
wet cloth when necessary.
(The fusible plug breaks at 158°F [70°C]).
• Tighten the screw in 14 - 18 N·m* (11-13 lbf·ft) with 2
wrenches.
*1 N·m ≈ 10 kgf·cm
18. Removing the thermal protector (TRS))
(1) Remove the service panel. (See Photo 1)
(2) Remove the cover panel front. (See Photo 1)
(3) Pull out the lead wire of high pressure switch and discon
nect the connector, 63H (yellow) from the multi controller
board in the electrical parts box. (See Photo 11)
(4) Remove the comp felt covering the compressor. (See
Photo 13)
(5) Loosen the clamp or band for the lead wire of the electri-
cal parts box and separator.
(6)
Pull out the thermal protector (TRS) from the holder. (See
Photo 19)
19. Removing the fuse holders
(1) Remove the service panel. (See Photo 1)
(2) Remove 2 screws (4 x 10) for cont base to remove the
cont base. (See Figure 4)
(3) Remove the fuse covers. (See Figure 5)
(4) Remove screws (3 x 12) for fuse holders to remove the
fuse holders. (See Figure 5 and Photo 20)
Notes:
1. Bracket, circuit board and other parts can get deformed
when inserting and removing the fuse cover.
2. Remove the fuse cover in the way that surrounding parts
will not be affected.
OCH811A
PHOTOS/FIGURES
Photo 18
Fusible plug
Photo 19
Thermal protector
(TRS)
Photo 20
Figure 4
167
Fuse holders
Figure 5
cont base
screws for
cont base
(4×10)
fuse covers
screws for
fuse holders
(3×12)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents