(2) Method for Obtaining the Equivalent Piping Length
Equivalent length = (length of piping to farthest indoor unit) + (0.99 × number of bends in the piping) (ft)
4-5-1. Correction of Heating Capacity for Frost and Defrosting
If heating capacity has been reduced due to frost formation or defrosting, multiply the capacity by the appropriate correction
factor from the following table to obtain the actual heating capacity.
Correction factor diagram
Outdoor Intake temperature <W.B.°F (°C)>
Correction factor
OCH811A
PUMY-HP36NKMU2
PUMY-HP42NKMU2
PUMY-HP48NKMU2
50
100
150
200
Piping equivalent length (ft)
<Heating>
20
40
60
80
100
Piping equivalent length (ft)
43(6)
37(4)
36(2)
1.00
0.98
0.89
<Heating>
250
300
350
400
120
140
160
180
32(0) 28(−2) 25(−4) 21(−6) 18(−8) 14(−10) 5(−15) −4(−20) −13(−25)
0.88
0.89
0.90
0.95
34
450
500
550
600
200
220
240
260
0.95
0.95
0.95
0.95
0.95