Connecting to the RS-232C Port at the Host
Note
58
Settings at the Host
The setting methods for each Unit are as follows:
Connecting to a C-series C200HS, C200HX/HG/HE(-Z)E, CPM1, CPM2A,
CPM2C, CQM1, CQM1H, or SRM1
PLC Setup Settings
Write the PLC Setup (in the DM Area) settings directly from a Programming
Device (e.g., SYSMAC Support Software) according to the host model and
port.
Host Model
RS-232C port of C200HS, C200HX/
HG/HE(-Z)E, CPM2A, CPM2C,
CQM1, CQM1H, SRM1
Port A of C200HX/HG/HE(-Z)E (See
note 1.)
Port 1 of CQM1H (See note 2.)
Port B of C200HX/HG/HE(-Z)E (See
note 1.
CPM1
(1) RS-232C port of the Communications Board
(2) RS-232C port of the Serial Communications Board
For details on operations relating to the PLC Setup, refer to the manual for the
PLC that is used.
Connecting to a CPM2C
The CPM2C PLCs do not have the same kind of port connectors found on CS/
CJ-series PLCs. The CPM2C's communications port handles both RS-232C
and peripheral port connections, which are divided internally. Therefore, when
using the CPM2C, it is necessary to select RS-232C or peripheral port con-
nections, according to the kind of cable and port (on the cable) used, as
shown in the following table. Refer to the CPM2C Operation Manual for more
details.
Port connecting to PT
RS-232C port (D-Sub 9-pin) of CPM2C-CN111
Peripheral port of CPM2C-CN111
RS-232C port (D-Sub 9-pin) of CS1W-CN118
Peripheral port of CS1W-CN114
Peripheral port
CPM2C-CN111
CPM2C
RS-232C port
(D-Sub 9-pin, female)
Setting the DIP Switches on the Front of a C200HX/HG/HE(-Z)E, CQM1,
CQM1H
When using a C200HX/HG/HE(-Z)E, CQM1, or CQM1H, the DIP switches on
the front panel must be set as shown below in order to make the settings in
the PLC Setup (data memory) effective.
Word
Writing Value
DM6645
4000
DM6555
DM6550
DM6650
Built-in RS-232C port settings
Peripheral port settings
Built-in RS-232C port settings
Peripheral port settings
CS1W-CN118 CPM2C
RS-232C port
(D-Sub 9-pin, female)
Section 2-6
Setting
Use 1:1 NT
Link
PLC Setup
CPM2C
CS1W-CN114
Peripheral port