4.4. G5 Operator Interface

4.4.1. Download and Install the G5 Operator Interface

The G5 Operator Interface is used to access the Nuvation Energy BMS. The latest Operator Interface
release will be available online at:
support@nuvationenergy.com
The G5 Operator Interface currently supports the most recent versions of Mozilla
Firefox and Google Chrome. Other browsers such as Internet Explorer are not
supported. Please install a supported browser before attempting to access the
Operator Interface.

4.4.2. Connect to the G5 Operator Interface

Ensure your computer is connected directly to the G5 Stack Switchgear via an Ethernet cable. You will
need to configure the network adapter on your computer to match the settings on your G5 Stack
Switchgear.
Identify the Battery Management System IP
By default, G5 Stack Switchgear is configured with a static IP address of 192.168.1.21, unless noted
otherwise on a label on the G5 Stack Switchgear.
Identify the parts of the Battery Management System's IP Address
The IP address has two parts - the network ID and the host ID.
Write down the network ID and host ID parts of the Battery Management System's IP address.
Determine a valid IP address to assign to the PC
The Network ID for the PC IP address must be the same as the Battery Management System. The
Host ID number can be any number from 2 to 255 as long at it is not the same as the Host ID of
the Battery Management System. For example if the Battery Management System IP address is
192.168.1.21, the IP address of the PC could be 192.168.1.12 or 192.168.1.49 or any 192.168.1.x
where x is not 21.
If you have multiple stacks, note down the Host ID from the IP address of each
stack's Battery Management System. The Host ID number assigned to the PC
Document ID: NE-DS-011
Nuvation Energy G5 High-Voltage BMS - NUVG5 Product Manual
https://www.nuvationenergy.com
for a copy.
Browser Compatibility
Figure 20. Parts of an IP address
33
In the interim, please contact
Rev 1.0, 2023-05-19
G5 Faraday