Mitsubishi Electric FR-D720-0.4K Instruction Manual page 198

Hide thumbs Also See for FR-D720-0.4K:
Table of Contents

Advertisement

Communication operation and setting
REMARKS
Set 65520 (HFFF0) as a parameter value "8888" and 65535 (HFFFF) as "9999".
For the instruction codes HFF, HEC and HF3, their values are held once written but cleared to zero when an inverter reset or all
clear is performed.
Example) When reading the C3 (Pr. 902) and C6 (Pr. 904) settings from the inverter of station 0
Computer Send Data
1)
ENQ 00 FF 0 01 82
2)
ENQ 00 EC 0 01 7E
3)
ENQ 00 5E 0 0F
4)
ENQ 00 60 0 FB
To read/write C3 (Pr. 902) and C6 (Pr. 904) after inverter reset or parameter clear, execute from 1) again.
List of calibration parameters
Parameter
C2 (902)
Terminal 2 frequency setting bias frequency
C3 (902)
Terminal 2 frequency setting bias
Terminal 2 frequency setting gain
125 (903)
frequency
C4 (903)
Terminal 2 frequency setting gain
C5 (904)
Terminal 4 frequency setting bias frequency
C6 (904)
Terminal 4 frequency setting bias
Terminal 4 frequency setting gain
126 (905)
frequency
C7 (905)
Terminal 4 frequency setting gain
[Special monitor selection No.]
Refer to page 129 for details of the monitor description.
Data
Description
Output frequency/speed ∗1, ∗4
H01
Output current ∗4
H02
Output voltage ∗4
H03
Frequency setting/speed setting ∗1
H05
H08
Converter output voltage
H09
Regenerative brake duty
Electronic thermal relay function
H0A
load factor
H0B
Output current peak value
H0C
Converter output voltage peak value
H0E
Output power
Input terminal status ∗2
H0F
∗1
When "0.01 to 9998" is set in Pr. 37 and "01" in instruction code HFF, the data format is 6 digits (E2).
∗2
Input terminal monitor details (when the terminal is ON: 1, when the terminal is OFF: 0, —: undetermined value)
b15
∗3
Output terminal monitor details (when the terminal is ON: 1, when the terminal is OFF: 0, —: undetermined value)
b15
∗4
The monitored values are retained even if an inverter fault occurs. Resetting will clear the retained values.
.... Specifications differ according to the date assembled. Refer to page 298 to check the SERIAL number.
196
Inverter Send Data
ACK 00
ACK 00
STX 00 0000 ETX 25
STX 00 0000 ETX 25
Instruction
Code
Name
5E DE
5E DE
5F
5F
60
60
61
61
Unit
0.01Hz/
0.001
0.01A
0.1V
0.01Hz/
0.001
0.1V
0.1%
0.1%
0.01A
0.1V
0.01kW
Description
Set "H01" to the expansion link parameter.
Set "H01" to second parameter changing.
C3 (Pr. 902) is read. 0% is read.
C6 (Pr. 904) is read. 0% is read.
Parameter
Frequency setting voltage bias frequency
1
C22(922)
(built-in potentiometer)
1
Frequency setting voltage bias (built-in
C23(922)
DF
1
potentiometer)
Frequency setting voltage gain frequency
DF
1
C24(923)
(built-in potentiometer)
E0
1
Frequency setting voltage gain (built-in
E0
1
C25(923)
potentiometer)
E1
1
E1
1
Data
Output terminal status ∗3
H10
H14
Cumulative energization time
H17
Actual operation time
H18
Motor load factor
H19
Cumulative power
H34
PID set point
H35
PID measured value
H36
PID deviation
H3D
Motor thermal load factor
H3E
Inverter thermal load factor
H3F
Cumulative power 2
H40
PTC thermistor resistance
RH
SO
Name
Description
RM
RL
ABC
Instruction
Code
16
96
9
16
96
9
17
97
9
17
97
9
Unit
1h
1h
0.1%
1kWh
0.1%
0.1%
0.1%
0.1%
0.1%
0.01kWh
0.01kΩ
b0
STR
STF
b0
RUN