Specifications

■ Standard Models
Specifications
Items
General-purpose
Controller
61F-@ (TDL)
(see note
Controlling materials
For control of ordi-
and operating condi-
nary purified water
tions
or sewage water
Supply voltage
100, 110, 120, 200, 220 or 240 VAC; 50/60 Hz
Operating voltage range 85% to 110% of rated voltage
InterElectrode voltage 8 VAC
InterElectrode current Approx. 1 mA AC max.
Power consumption
61F-G@: 3.5 VA max.; G1F-G1@, G1F-G2@, or G1F-I@: 5.5 VA max.; G1F-G3@: 7.5 VA max.; G1F-G4@: 14.5 VA max.
InterElectrode operate
0 to approx. 4 kΩ
resistance
Approx. 15 k to ∞ Ω Approx. 15 k to
InterElectrode release
resistance
Cable length
1 km max.
(see note 3)
Control output
2 A, 220 VAC (Inductive load: cosφ = 0.4)
5 A, 220 VAC (Resistive load)
Ambient temperature
Operating: –10 to 55°C (–10 to 70°C for 61F-@T)
Ambient humidity
Operating: 45% to 85% RH
Insulation resistance
100 MΩ min. (at 500 VDC)
(see note 4)
Dielectric strength
2000 VAC, 50/60 Hz for 1 min.
(see note 4)
Life expectancy
Electrical:
Mechanical: 5,000,000 operations min.
Weight
61F-G@: Approx. 380 g, G1F-G1@, G1F-G2@, or G1F-I@: Approx. 750 g; G1F-G3@: Approx. 930 g;
G1F-G4@: Approx. 1,710 g
Note: 1. The @ in the model name represents G, G1, G2, G3, G4, and I.
2. The suffix "TDL" attached to the model name represents models designed for tropical regions (storage humidity of 45% to 90%). For de-
tails, refer to Safety Precautions for Floatless Level Controllers.
3. The length when using completely-insulated, 600-V, 3-conductor (0.75 mm
the cable diameter or number of conductors becomes larger. For details, refer to Safety Precautions for Floatless Level Controllers.
4. The insulation resistance and dielectric strength indicate values between power terminals and Electrode terminals, between power ter-
minals and contact terminals, and between Electrode terminals and contact terminals.
5. Possible to use with 15 kΩ or less, however, this may cause reset failure.
6. High-sensitivity Controllers use advanced operation.
When the power supply voltage is applied, if there are some liquids between the electrodes (ground and operation electrodes), the inter-
nal relay will not operate.
When the power supply voltage is applied, if there are no liquids between the electrodes (ground and operation electrodes), the internal
relay will operate.
High-
temperature
Controller
61F-@T
1 and 2)
(see note 1)
For control of ordi-
nary purified water
or sewage water
in cases where the
ambient tempera-
ture is high.
0 to approx. 5 kΩ 0 to approx.
∞ Ω
600 m max.
500,000 operations min.
Long-distance
High-sensitivity
Controllers
Controllers
61F-@L 2KM
61F-@H
(for 2 km)
(see note 1)
61F-@L 4KM
(for 4 km)
(see note 1)
For control of ordi-
For control of liq-
nary purified water
uids with high
in cases where the
specific resis-
distance between
tance such as dis-
sewage pumps
tilled water
and water tanks or
between receiver
tanks and supply
tanks is long or
where remote
control is required.
24 VAC
Approx. 15 kΩ to
1.8 kΩ (for 2 km)
70 kΩ
0 to approx.
(see note 5)
0.7 kΩ (for 4 km)
4 k to ∞ Ω (for
Approx. 300 k to
∞ Ω
2 km)
2.5 k to ∞ Ω (for
4 km)
2 km max.
50 m max.
4 km max.
2
) cabtire cables. Usable cable lengths will become shorter as
• Advanced Operation
With advanced operation, the internal relay
operates as soon as control power is
supplied to the G1F and is reset when current
flows between the poles. Wiring is the same
as for models with sequential operation.
61F-G@
Low-sensitivity
Two-wire
Controller
Controller
61F-@D
61F-@R
(see note 1)
(see note 1)
For control of liq-
For control of ordi-
uids with low spe-
nary purified water
cific resistance
or sewage water
such as salt water,
used in combina-
sewage water,
tion with Two-wire
acid chemicals, al-
Electrode Holder
kali chemicals
(incorporating a
resistor of 6.8 kΩ)
8 VAC
0 to approx.
0 to approx. 1.1 kΩ
1.8 kΩ
Approx. 5 k to ∞ Ω Approx. 15 k to
∞ Ω
1 km max.
800 m max.
2