8-pin 61F-GP-N8 61F-GP-N8L 2KM 61F-GP-N8L 4KM Type High-sensitivity Low-sensitivity Two-wire Model Model Model 8-pin 61F-GP-N8H 61F-GP-N8D 61F-GP-N8R 61F-GP-N8HY Note: When ordering, specify the desired operating voltage at the end of the model number. Example: 61F-GP-N [220 VAC] Desired supply voltage...
Page 3
61F-GP-N@ Internal Circuit Diagrams 61F-GP-N/-NT/-NL/-ND 61F-GP-NH 61F-GP-NR Power supply Power supply Power supply Control circuit Control circuit Control circuit 24 V 24 V 24 V (See note.) (See note.) Note: When applying a self-holding circuit, short between terminals 5 and 6 and use terminal 7 as E...
Page 4
61F-GP-N@ ■ Connections Automatic Water Supply and Compact, Plug-in Type Drainage Control 61F-GP-N Dimensions: page 14 Automatic Water Supply Control Automatic Drainage Control Connections Connections 61F-GP-N 61F-GP-N Commercial Voltage Commercial Voltage MCCB MCCB Control Control 24 V 24 V circuit...
Page 5
Electrode (the longest Electrode, terminal 4). Principles of Operation • Terminals 6 and 7, and terminals 10 and 11 on the lower -limit 61F-GP-N are shorted when the water level reaches E (indicator ON). • Terminals 6 and 7, and terminals 10 and 11 on the intermediate 61F-GP-N are shorted when the water level reaches E (indicator ON).
Page 6
61F-GP-N@ Replacing 61F-G3N Functions (Automatic Water Compact, Plug-in Type Supply Control with Abnormal Water Increase and 61F-GP-N Water Shortage Alarms) Dimensions: page 14 Replacing 61F-G3N Functions Connections Water shortage Pump control Full tank Commercial Voltage 61F-GP-N 61F-GP-N 61F-GP-N Control Control...
Page 7
61F-GP-N@ Two-Wire Connections Compact, Plug-in Type Automatic Water Supply and Drainage Control 61F-GP-NR Dimensions: page 14 Automatic Water Supply Control Automatic Drainage Control Connections Connections Commercial Voltage Commercial Voltage 61F-GP-NR 61F-GP-NR MCCB MCCB Control Control 24 V 24 V circuit...
Page 8
When supplying power from N-phase to the Controller in three-phase four-line circuit, refer to the following diagrams. Line voltage (R-S, S-T, or R-T): 380 or 415 VAC Phase voltage (N-R, N-S, or N-T): 220 or 240 VAC 61F-GP-N@ 220 or 240 VAC 61F-GP-N Power source 380 or 415 VAC...
Page 10
61F-GP-N@ Internal Circuit Diagrams 61F-GP-N8R 61F-GP-N8/-N8L/-N8D/-N8HY 61F-GP-N8H Power supply Power supply Power supply Control circuit 24 V Control circuit 24 V Control circuit 24 V 8 V (see note) 24 V Note: 24 V for the 61F-GP-N8HY. 61F-GP-N8Y 61F-GP-N8-V50 Power supply...
Page 11
61F-GP-N@ Automatic Water Supply and Drainage Control Compact, Plug-in Type 61F-GP-N8 Dimensions: page 14 Automatic Water Supply Control Automatic Drainage Control Connections Connections 61F-GP-N8 61F-GP-N8 Commercial Voltage Commercial Voltage MCCB MCCB Control 24 V 24 V Control circuit Power circuit...
Page 12
61F-GP-N@ Two-Wire Connections Compact, Plug-in Type Automatic Water Supply and Drainage Control 61F-GP-N8R Dimensions: page 14 Water Supply Automatic Drainage Connections Connections Commercial Voltage Commercial Voltage 61F-GP-N8R 61F-GP-N8R MCCB MCCB Control Control 24 V 24 V circuit circuit Power Power...
Page 13
61F-GP-N@ ■ Connection with Three-phase Four-line Circuit When supplying power from N-phase to the Controller in three-phase four-line circuit, refer to the following diagrams. Line voltage (R-S, S-T, or R-T): 380 or 415 VAC Phase voltage (N-R, N-S, or N-T): 220 or 240 VAC...
61F-GP-N@ Dimensions Note: All units are in millimeters unless otherwise indicated. 61F-GP-N, -NT, -NL, -NH, -ND, -NR, -N -TDL, -N14, -N15, -NH3 When mounting a Display Unit to a PF113A Surface-mounting Socket, secure the PF113A with the groove facing toward the bottom and then connect the 61F-GP-N the PFC-N8 accessory.
Page 15
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron disclaims all other warranties, express or implied.