SECTION 2 CompoWay/F Communications Protocol

2.4 Response Code List

Normal Completion
Response
code
0000
Normal completion
Error Occurred
Response
code
0401
Unsupported command
1001
Command too long
1002
Command too short
1101
Area type error
1003
Number of elements/data mis-
match
110B
Response too long
1100
Parameter error
3003
Read-only error
2203
Operation error
34
Name
No errors were found.
Name
The service function for the relevant command is
not supported.
The command is too long.
The command is too short.
Wrong variable type
The amount of data does not match the number
of elements.
The response exceeds the communications
buffer size (when the number of elements is
larger than 0002).
• Bit position is not 00.
• The write data is out of the setting range.
• The command code or related information in
the operation command is wrong.
• The bit address is out of range.
Variable type "C0" was written to.
Unit error (Memory error occurred, or unused
command was sent.)
Description
Description
Error
detection
priority
None
Error
detection
priority
1
2
3
4
5
6
7
8
9

Advertisement