Specifications

MODEL
Battery voltage
INVERTER OUTPUT
Rated Power
Surge Rating (20ms)
Waveform
Nominal Output Voltage
Output Frequency
Inverter Efficiency(Peak)
Line Mode Efficiency
Power Factor
SOLAR CHARGER
Maximum PV Charge Current
DC Voltage
Maximum PV Array Power
MPPT Operating Voltage(VDC)
Max. PV Array Open Circuit
Voltage
Maximum Efficiency
DC Input
Low DC Cut-Off Voltage (Only
Lead Acid)
Low DC Warning Voltage (Only
Lead Acid)
Low DC Warning Return
Voltage (Only Lead Acid)
Low DC Warning SOC (Only Li)
Low DC Warning Return SOC
(Only Li)
Low DC Cut-off SOC (Only Li)
Cold Start SOC (Only Li)
High DC Recovery Voltage
High DC Cut-Off Voltage
AC INPUT
Voltage
Selectable Voltage Range
Frequency Range
Maximum Charge Current
BYPASS & PROTECTION(Grid & Generator)
Typical Transfer Time
Overload Protection (SMPS
Load)
Output Short Circuit Protection
MECHANICAL SPECIFICATIONS
Dimensions (W*H*D)
30
SPF 4000T DVM
SPF 5000T DVM
48VDC
48VDC
4KW
5KW
12KW
15KW
Pure sine wave/ same as input (bypass mode)
104V-110V-115V-120Vac / 208V-220V-230V-240Vac(+/-10% RMS)
80A
5000W
Default @load<20%: 42.0V; @20%≤load<50%: 40.8V; @load≥50%: 38.4V
AGM:60V, FLD:62V, USE or Li Mode: C.V. Voltage + 4.0V
154~272VAC(for appliances ), 184~272VAC(for UPS)
40A
50A
540*360*218mm
SPF 6000T DVM SPF 8000T DVM SPF 10000T DVM SPF 12000T DVM
48VDC
6KW
18KW
50Hz/60Hz(+/-0.3 Hz)
>85%
>95%
1.0
48V
60-145V
150VDC
97.5%
(Based on Program 21, 40Vdc~48Vdc settable)
Low DC Cut-Off Voltage +2Vdc
>48V
<Low DC Cut-off SOC +5%
>Low DC Cut-off SOC +15%
Default 20%, 5%~50% Settable
>Low DC Cut-off Soc+10%
58VDC
240VAC
50Hz/60Hz (Auto sensing)
60A
10ms
Circuit breaker
Circuit breaker
48VDC
48VDC
8KW
10KW
24KW
30KW
120A
7000W
70A
80A
650*380*225mm
48VDC
12KW
36KW
100A