Product Specifications 10 - Growatt WIT 50K-A User Manual

Storage/hybrid inverter
Table of Contents

Advertisement

Error Code
Description
High DC component in
Error 606
output voltage
EPS Overload
Off-grid output overload
Off-grid parallel signal
Error 608
abnormal
101
Suggestion
1. Restart the inverter.
2. If the error message persists, please
contact Growatt support.
1. Restart the inverter.
2. If the error message persists, please
contact Growatt support.
1. Check if the communication cables
are properly connected.
2. If the error message persists, please
contact Growatt support.

Product Specifications 10

Table 10.1 WIT 50/63/75/100K-A Specification
Model
WIT 50K-A
Specifications
Battery data(DC)
Continuous charging /
56700W
discharging power
Battery voltage range
600-1000V(for 3P3W )/ 680-1000V(for 3P4W)
Recommended battery
voltage
Max. charging and
83.3A
discharging current
BMS communication
Output data(AC)
Rated AC output power
50000W
Max. AC apparent power
55000VA
Nominal AC voltage
AC voltage range
AC grid frequency
AC grid frequency range
75.6A@220V
Rated output current
72.5A@230V
83.3A@220V
Max. output current
79.7A@230V
Power factor (@nominal
power)
Adjustable power factor
THDi
AC grid connection type
Backup power(AC)
Rated AC output power
50000W
Max. AC apparent power
60000VA
Rated AC output voltage
Nominal AC output
frequency
90.9A@220V
Max. output current
87A@230V
WIT 63K-A
WIT 75K-A
WIT100K-A
71400W
85100W
113500W
768V
105A
125A
167A
RS485/CAN
63000W
75000W
100000W
69300VA
82500VA
110000VA
220V/230V/240V(L-N)
380V/400V/415V(L-L)
-15%~+10%
50/60 Hz
45~55Hz/55-65 Hz
95.5A@220V
113.6A@220V
151.5A@220V
91.3A@230V
108.7A@230V
144.9A@230V
105A@220V
125A@220V
166.7A@220V
100.4A@230V
119.6A@230V
159.4A@230V
>0.99
(1 leading~1 lagging)
<3%
3P+PE/3P+N+PE
63000W
75000W
100000W
75600VA
90000VA
120000VA
220V/230V/240V(L-N)
380V/400V/415V(L-L)
50/60 Hz
114.5A@220V
136.4A@220V
181.8A@220V
109.6A@230V
130.4A@230V
173.9A@230V
102

Advertisement

Table of Contents