AC Input/Output Connection

CAUTION! !
Before connecting to AC input power source, please install a separate AC breaker between inverter and AC input
power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected
from over current of AC input. The recommended spec of AC breaker is 40A for 4KW~6KW, 80A for 8KW~12KW.
There are two terminal blocks with "IN" and "OUT" markings. Please do NOT mis-connect input and output
connectors.
WARNING! !
All wiring must be performed by a qualified personnel.
It‟s very important for system safety and efficient operation to use appropriate cable for AC input connection. To
reduce risk of injury, please use the proper recommended cable size as below.
Suggested cable requirement for AC wires
Model
4KW/5KW
6KW/8KW
10KW/12KW
AC Wiring
240Vac output
Input:
HOT1+ HOT2+Ground
Output:
HOT1+ HOT2
120Vac output
Input:
HOT1+ HOT2+Ground
Output:
HOT1+ N or HOT2+ N
Please follow below steps to implement AC input/output connection:
1. Before making AC input/output connection, be sure to open DC protector or disconnector first.
2. Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm.
3. Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. Be
sure to connect PE protective conductor
8
Gauge
10 AWG
8 AWG
6 AWG
first.
Torque Value
1.4~ 1.6 Nm
1.4~ 1.6 Nm
1.6~ 1.8 Nm