Maytag Amana SXV9 Series Service And Troubleshooting page 96

Inverter air conditioner condenser units with r-410a refrigerant
Table of Contents

Advertisement

Troubleshooting
Error Code:
70 - EEV open circuit
Applicable Models:
DV**FEC / DV**PEC / CAPE(A) /
CHPE
Method of Error Detection:
Check indoor EEV coil connection
Error Decision Conditions:
EEV connector not detected
96
Board reads
70 on the
display
Is the indoor
Is the indoor
No
EEV connection
EEV connection
plugged into the
plugged into the
board?
board?
Yes
Is the indoor EEV
harness extension
No
plugged in and not
corroded? (located in
the blower
compartment)?
Yes
Error Code - 70
Plug the connection into the
correct termination as shown on
the wiring diagram
Replace the EEV coil
If fault code is still present
replace the board.