Checking Subcooling - Maytag Amana SXV9 Series Service And Troubleshooting

Inverter air conditioner condenser units with r-410a refrigerant
Table of Contents

Advertisement

SERVICING
CHECKING SUPERHEAT
Refrigerant gas is considered superheated when its tem-
perature is higher than the saturation temperature corre-
sponding to its pressure. The degree of superheat equals
the degrees of temperature increase above the saturation
temperature at existing pressure. See Temperature - Pres-
sure Chart on following pages.
1. Run system at least 10 minutes to allow pressure to
stabilize.
2. For best results, temporarily install a thermometer on the
liquid line at the liquid line service valve and 4-6" from
the compressor on the suction line. Ensure the thermom-
eter makes adequate contact and is insulated for best
possible readings. Use liquid line temperature to deter-
mine sub-cooling and vapor temperature to determine
superheat.
NOTE: An optional method is to locate the thermometer
at the suction line service valve. Ensure the thermometer
makes adequate contact and is insulated for best possible
readings.
3. Refer to the superheat table provided for proper system
superheat. Add charge to lower superheat or recover
charge to raise superheat.
Superheat Formula = Suct. Line Temp. - Sat. Suct.Temp.
EXAMPLE:
a. Suction Pressure = 143 PSIG
b. Corresponding Temp. = 50°F.
c. Thermometer on Suction Line = 58°F.
To obtain the degrees temperature of superheat, subtract
50.0 from 58.0°F.
The difference is 8° Superheat. The 8° Superheat would fall
in the ± range of allowable superheat.

CHECKING SUBCOOLING

Refrigerant liquid is considered subcooled when its tem-
perature is lower than the saturation temperature corre-
sponding to its pressure. The degree of subcooling equals
the degrees of temperature decrease below the saturation
temperature at the existing pressure.
1. Attach an accurate thermometer or preferably a thermo-
couple type temperature tester to the liquid service valve
as it leaves the condensing unit.
2. Install a high side pressure gauge on the high side (liq-
uid) service valve at the front of the unit.
3. Record the gauge pressure and the temperature of the
line.
22
4. Review the technical information manual or specification
sheet for the model being serviced to obtain the design
subcooling.
5. Compare the hi-pressure reading to the "Required Liquid
Line Temperature" chart. Find the hi-pressure value on
the left column. Follow that line right to the column under
the design subcooling value. Where the two intersect is
the required liquid line temperature.
Alternately you can convert the liquid line pressure
gauge reading to temperature by finding the gauge read-
ing in the R-410A Pressure vs. Temperature Chart, find
the temperature in the °F. Column.
6. The difference between the thermometer reading and
pressure to temperature conversion is the amount of
subcooling.
Add charge to raise subcooling. Recover charge to lower
subcooling.
Subcooling Formula = Sat. Liquid Temp. - Liquid Line
Temp.
NOTE: To adjust subcooling, follow the sequence of S-108.
EXAMPLE:
a. Liquid Line Pressure = 417 PSIG
b. Corresponding Temp. = 120°F.
c. Thermometer on Liquid line = 109°F.
To obtain the amount of subcooling subtract 109°F from
120°F.
The difference is 11° subcooling. See the specification
sheet or technical information manual for the design sub-
cooling range for your unit.
There are other causes for high head pressure which may
be found in the "Cooling / Heating Analysis Chart."
If other causes check out normal, an overcharge or a sys-
tem containing non-condensables would be indicated.
If this system is observed:
1. Start the system.
2. Remove and capture small quantities of gas from the
suction line dill valve until the head pressure is reduced
to normal.
3. Observe the system while running a cooling perfor-
mance test. If a shortage of refrigerant is indicated, then
the system contains non-condensables.
Charging Table
OD Ambient Temp
<65°F
(degF)
Subcooling
Weigh in
(degF)
Charge
SUPERHEAT AND SUBCOOLING ADJUSTMENT ON
TXV APPLICATIONS
65°F to 105°F
>105°F
Weigh in
2T to 5T:8°F ±1°F
Charge

Advertisement

Table of Contents
loading

Table of Contents