Maytag Amana SXV9 Series Service And Troubleshooting page 114

Inverter air conditioner condenser units with r-410a refrigerant
Table of Contents

Advertisement

ACCESSORIES
AMVE
HEATER KIT
MODELS
AMVE24BP14**
X
AMVE36CP14**
AMVE48DP14**
AMVE60DP14**
*Revision level that may or may not be designated.
NOTE: Airflow selection should meet the minimum requirements as mentioned in the air handler Installation instructions.
For heater kit installation, it is important to set the capacity of the electric heater at Set-up menu on the thermostat and
DIP switch on indoor unit control board. For more information, please see indoor unit I/O manual.
9
Htr kW
3
ON
5
ON
6
ON
8
ON
10
OFF
15
OFF
19*
OFF
20
21 or 25*
OFF
NOTE: Airflow data shown applies to the electric heat only in either legacy mode or communicating mode operation.
NR- Not rated
+For match up with a 2 ton outdoor unit: Heater kit application shall not exceed 10 kW.
Airflow for 5 kW up to 10 kW heater kits shall be set to 850 cfm speed tap of ON-ON-ON.
++For match up with a 3 ton outdoor unit: Heater kit application shall not exceed 15 kW.
Airflow for 5 kW up to 15 kW heater kits shall be set to 1300 cfm speed tap of ON-OFF-ON.
Airflow for 5 kW up to 20 kW heater kits shall be set to 1500 cfm speed tap of ON-OFF-OFF
** 3 kW heater kit is not applicable for this indoor application.
114
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
ELECTRIC HEAT AIRFLOW TABLE
10
11
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
X
X
X
X
X
X
X
X
X
X
X
X
AMVE24BP14**
AMVE36CP14**
730
850**
780
1250
850
1300
950
1500
1025
1550
1720
NR
NR
NR
NR
1800
NR
NR
X
X
X
X
X
X
X
X
X
AMVE48DP14**
NR
1250
1300
1500
1550
1720
NR
1815
1850
X
X
X
AMVE60DP14**
NR
1250
1300
1500
1550
1780
NR
1850
1850