6. Mode Settings

6. Mode Settings
Setting mode 1
<Operating procedure>
1
Press and hold the
(VENTILATION) button simultaneously for 4
seconds or longer.
2
Press the temperature setting
buttons to change the item code. The item codes
and setting data are shown in the table of "List of
Item Codes" on the next page.
3
Press the timer time
change the setting data.
To confirm the changed setting data, press the
button.
(At this time, "
and remains lit.)
4
During this mode, "
blinking. The outdoor unit address display section
displays "ALL," the item code and number (DN
value in the table), and the setting data (6 digits).
(The setting data is displayed in 6 digits. The
display changes between the first 3 digits (Fig. A )
and the last 3 digits (Fig. B
When the first 3 digits are displayed, the bottom dot
4
of the colon is illuminated.)
5
To exit the setting mode, press the
button.
DN
Snowfall sensor usage
Outdoor unit fan Quiet
mode
Energy saving mode
Energy saving operation
plug
Demand 1 current
Demand 2 current
High static pressure mode
(CHECK) button and
and
and
buttons to
" display stops blinking
" is displayed,
).
(CHECK)
Parameter
000 = Sensor input not present. Control is performed.
001 = Sensor input present. Control is performed.
002 = Sensor input not present. Control is not performed.
003 = Sensor input present. Control is not performed.
000 = Disabled
002 = Quiet mode 2
004 = Quiet mode 4 ...
000 = None
001 = Discharge temp. control only (Mode 3)
002 = Demand only (Mode 2)
003 = Discharge temp. control + Demand (Mode 1)
000 = Independent
001 = All indoor units linked
000 = 0%
130 = 130% ...
000 = 0%
130 = 130% ...
000 = Disabled
* Charge when the external static pressure is increased to over 30 Pa.
Outdoor Unit Maintenance Remote Controller
Outdoor Unit Maintenance Remote Controller
A
Display of fi rst 3 digits
5
1
3
B
Display of last 3 digits
5
1
A
and
B
are displayed alternately.
(Example shows display of 000 001.)
Description
001 = Quiet mode 1
003 = Quiet mode 3
012 = Quiet mode 12
040 = 40% ...
070 = 70% ...
-001 = no limit
040 = 40% ...
070 = 70% ...
-001 = no limit
001 = High static pressure mode
4 - 12
2WAY SYSTEM
2WAY SYSTEM
3
100 = 100% ...
100 = 100% ...