10. Compressor
Installation
(1)
Remove the 2 brazed tube caps (2 pieces) from the compressor.
(2)
Remove hexagonal caps from the compressor.
*
When removing the hexagonal caps, hold the fixing nut at the main unit side so as not to loose it with a
wrench or spanner. And then, loosen and remove the hexagonal cap.
2
(3)
Remove the oil equalizer tube connector parts along with the O-ring from the removed compressor and
mount them on the replaced new compressor.
(4)
Install the crankcase heater onto the new compressor.
(5) Temporary mount 2 cushion rubbers with bolts at the position as shown in the figure 25.
Set up the leg of the new compressor onto the 2 cushion rubbers.
(Temporary mounting: 2 locations
at back side, each 1 piece)
Hexagonal cap
Fixing nut
at the main unit side
Cushion rubbers
Bolts
Fig. 24
Front view
Fig. 25
2 - 32
3-WAY SYSTEM
Outdoor Unit Repair Procedures
Oil equalizer tube
connector parts
O-ring