Figure 2 5 - Heat Exchanger (Oil Cooler) Approximate Water Flow - Gardner Denver EBM99M 60 Operating And Service Manual

Electra-saver, electra-saver ii stationary base-mounted compressor
Table of Contents

Advertisement

DISCHARGE SERVICE LINE - The discharge service line connection on both water-cooled and air-
cooled units is made at the right hand corner of the unit, viewed from the opposite end from control panel
side. When manifolding two or more rotary screw units on the same line, each unit is isolated by the
check valve in the unit discharge line. If a rotary screw unit is manifolded to another compressor, be sure
the other compressor has a check valve in the line between the machine and the manifold. If a rotary
screw and a reciprocating compressor are manifolded together, an air receiver must be located between
the two units.
Discharge air used for breathing will cause severe injury or death.
Consult filtration specialists for additional filtration and treatment equipment to
meet health and safety standards.
BLOWDOWN VALVE PIPING - The blowdown valve is piped back into the airend between the inlet valve
and air filter.
HP
Model
EAM99E
60
EBM99N
EAM99E
75
EBM99N
EAP99L
100
EBP99L
* Flows exceeding "Maximum Water Flow" will cause severe erosion and will void unit warranty.
Figure 2-5 – HEAT EXCHANGER (OIL COOLER) APPROXIMATE WATER FLOW
HEAT EXCHANGER
Water Temperature to Heat
Exchanger
Gallons/minute
60° F
70° F
80° F
5.0
6.2
8.3
6.0
7.6
10.1
8.4
10.5
14.1
13-21-603
Maximum Water
Flow
Gallons/minute *
90° F
12.5
40.8
15.1
40.8
21.1
40.8
Page 18
Approximate Water
Pressure Drop @ 90° F
Water Temperature PSI
2.0
1.5
5.0

Advertisement

Table of Contents
loading

This manual is also suitable for:

Eam99eEap99lEbp99l

Table of Contents