Auxiliary Power Operation; Simultaneous Welding And Auxiliary Power Loads - Lincoln Electric DUAL VANTAGE 700 (AU) Operator's Manual

Table of Contents

Advertisement

DUAL VANTAGE
®
700 (AU)
TABLE B.5 DUAL VANTAGE
WELD
AMPS
WATTS
0
7,200
100
7,200
PLUS
200
7,200
300
7,200
400
7,200
500
6,400
600
TABLE B.6 DUAL VANTAGE
(Use the shortest length extension cord possible sized per the following table.)
Current
Voltage
Load
(Amps)
(Volts)
(Watts)
2.5
15
240
3,600

AUXILIARY POWER OPERATION

Start the engine and set the IDLER control switch to
the desired operating mode. Full power is available
regardless of the welding control settings, if no weld-
ing current is being drawn.
SIMULTANEOUS WELDING AND AUXIL-
IARY POWER LOADS
It must be noted that the above auxiliary power ratings
are with no welding load.
Simultaneous welding and power loads are specified
in table B.5.
700 (AU) SIMULTANEOUS WELDING AND POWER LOADS
®
1 PHASE
AMPS
30
30
OR
30
30
30
26
0
0
700 (AU) Extension Cord Length Recommendations
®
Maximum Allowable Cord Length in m (ft.) for Conductor Size
mm 14AWG 4.0
mm 12AWG 6.0
2
2
18
(60)
23
(75)
Conductor size is based on maximum 2.0% voltage drop.
3 PHASE
WATTS
AMPS
20,000
28
20,000
28
20,000
28
16,800
23
12,000
16
6,400
9
0
0
mm 10AWG 10.0
mm 8AWG 16.0
2
2
46
(150)
69
B-10
BOTH 1 AND 3 PHASE
WATTS
AMPS
------
28
------
28
------
28
------
23
7,200
------
6,400
------
0
------
mm 6AWG 25.0
2
107
183
(225)
(350)
OPERATION
mm 4AWG
2
(600)

Advertisement

Table of Contents
loading

This manual is also suitable for:

12299

Table of Contents