Auxiliary Power Operation - Lincoln Electric Dual Maverick 200 Operator's Manual

Table of Contents

Advertisement

DUAL MAVERICK
®
200/200X

AUXILIARY POWER OPERATION

Start the engine and set the IDLER control switch to the desired
operating mode. Full power is available regardless of the welding
control settings, if no welding current is being drawn.
For heavy loads set to HIGH IDLE and maximum weld output for
maximum starting power.
SIMULTANEOUS WELDING AND AUXILIARY POWER
LOADS
It must be noted that the specified auxiliary power ratings are with
no welding load.
Simultaneous welding and power loads are specified in Table B.3.
TABLE B.3 DUAL MAVERICK
Simultaneous Each Side
Dual Current
23.9
54.1
114
145.3
177.2
196.6
200
225
Simultaneous Each Side
Dual Current
23.9
54.1
114
145.3
177.2
196.6
200
225
®
200/200X SIMULTANEOUS WELDING AND POWER LOADS
Simultaneous Welding and Power Loads (120/240V AUX)
Single Current
45.8
100
200
250
300
330
400
450
Simultaneous Welding and Power Loads (120V AUX)
Single Current
45.8
100
200
250
300
330
400
450
Aux Power
10000
8600
5400
3500
1400
0
0
0
Aux Power
2400
2400
2400
2400
1400
0
0
0
B-7
OPERATION
Single Phase Amps
(240V)
41.7
35.8
22.5
14.6
5.8
0
0
0
Single Phase Amps
(120V)
20 + 20
20 + 20
20 + 20
20 + 9.2
11.67 + 0
0 + 0
0 + 0
0 + 0