DUAL VANTAGE
®
700 (AU)
2. Take necessary steps to assure load is limited to
the capacity of the DUAL VANTAGE
installing a 32 amp, 415 VAC three pole circuit
breaker. Loading above the rated output will reduce
output voltage below the allowable -10% of rated
voltage which may damage appliances or other
motor-driven equipment and may result in overheat-
ing of the DUAL VANTAGE
3. Install a 32 amp 3 phase plug to the triple-pole cir-
cuit breaker using 6.02mm (minimum) x 4 conductor
cable of the desired length.(1 x 32 amp / 415 V & 2
x 15 amp / 240 V, plugs are available in the optional
KA1373-2 plug kit).
4. Plug this cable into the 3 phase receptacle on the
DUAL VANTAGE
700 (AU) case front.
®
WARNING
• Only a licensed, certified, trained electrician
should install the machine to a premises or resi-
dential electrical system. Be certain that:
• The installation complies with the National
Electrical Code and all other applicable electri-
cal codes.
• The premises is isolated and no feedback into
the utility system can occur. Certain laws require
the premises to be isolated before the generator
is linked to the premises. Check your local
requirements.
------------------------------------------------------------------------
700 (AU) by
®
700 (AU) engine.
®
A-7
INSTALLATION