Chapter 3: Commissioning
One loop – two zones
Figure 13: One loop – two zones
Based on the example shown in Figure 13 above, configure the ECU as follows:
1. Select the two addresses, for example:
Extinguishing relay = address 025 on loop 1
Coincidence connection relay = address 046 on loop 1
Refer to "Guidelines to programming the ECU" on page 6 if required.
2. Use zone allocation routine to allocate the following devices:
1001 and 1002 to Zone 14
1024, 1027, and 1028 to Zone 15
3. Use I/O mapping routine to map the following:
Zone 14 to operate the extinguishing relay (1025)
Zone 15 to operate the coincidence connection relay (1046)
4. Program both the extinguishing relay (1025) and the coincidence connection
relay (1046) to single-knock/non-silencing operation mode.
Verify the programming by triggering a detector in each zone and checking that
the ECU functions correctly.
WARNING:
Make sure that the actuator is disconnected so as not to discharge
the cylinder.