Ziton ZP3-ECU Installation And Commissioning Manual page 33

Extinguishing control unit
Hide thumbs Also See for ZP3-ECU:
Table of Contents

Advertisement

One loop – multiple detectors
Figure 12: One loop – multiple detectors
Based on the example shown in Figure 12 above, configure the ECU as follows:
1. Select the two addresses, for example:
Extinguishing relay = address 025 on loop 1
Coincidence connection relay = address 046 on loop 1
Refer to "Guidelines to programming the ECU" on page 6 if required.
2. Use the I/O mapping routine to map the following devices:
1001, 1004, and 1008 to operate the extinguishing relay (1025)
1022 and 1027 to operate the coincidence connection relay (1046)
3. Program both the extinguishing relay (1025) and the coincidence connection
relay (1046) to single-knock/non-silencing operation mode.
4. Verify the programming by triggering two detectors, and one mapped to each
output, and checking that the ECU functions correctly.
WARNING:
Make sure that the actuator is disconnected so as not to discharge
the cylinder.
ZP3-ECU Extinguishing Control Unit Installation and Commissioning Manual
Chapter 3: Commissioning