Ziton ZP3-ECU Installation And Commissioning Manual page 31

Extinguishing control unit
Hide thumbs Also See for ZP3-ECU:
Table of Contents

Advertisement

Two loops with one zone in each loop
Figure 10: Two loops with one zone in each loop
Based on the example shown in Figure 10 above, configure the ECU as follows:
1. Select the two addresses, for example:
Extinguishing relay = address 005 on loop 1
Coincidence connection relay = address 026 on loop 2
Refer to "Guidelines to programming the ECU" on page 6 if required.
2. Use the zone allocation routine to allocate the following devices:
1001, 1002, and 1004 into Zone 14
2021, 2022, and 2025 into Zone 15
3. Use the I/O mapping routine to map the following:
Zone 14 to operate the extinguishing relay (1005)
Zone 15 to operate the ECU coincidence connection relay (2026)
Programme both the extinguishing relay (1005) and coincidence
connection relay (2026) to single-knock/non-silencing operation mode.
4. Verify the programming by triggering a detector in each zone and checking
that the ECU functions correctly.
WARNING:
Make sure that the actuator is disconnected so as not to discharge
the cylinder.
ZP3-ECU Extinguishing Control Unit Installation and Commissioning Manual
Chapter 3: Commissioning
23