Chapter 3: Commissioning
Two loops – detectors in each
Figure 11: Two loops – detectors in each
Based on the example shown in Figure 11 above, configure the ECU as follows:
1. Select the two addresses, for example:
Extinguishing relay = address 005 on loop 1
Coincidence connection relay = address 026 on loop 2
Refer to "Guidelines to programming the ECU" on page 6 if required.
2. Use the I/O mapping routine to map the following devices:
1001, 1002, and 1004 to operate the extinguishing relay (1005)
2021, 2022, and 2025 to operate the coincidence connection relay (2026)
3. Program both the extinguishing relay (1005) and the coincidence connection
relay (2026) to single-knock/non-silencing operation mode.
4. Verify the programming by triggering a detector in each loop and checking
that the ECU functions correctly.
WARNING:
Make sure that the actuator is disconnected so as not to discharge
the cylinder.
24
ZP3-ECU Extinguishing Control Unit Installation and Commissioning Manual