Addressing - Ziton ZP3-ECU Installation And Commissioning Manual

Extinguishing control unit
Hide thumbs Also See for ZP3-ECU:
Table of Contents

Advertisement

Chapter 3: Commissioning

Addressing

The ECU uses two addresses on the addressable loop. These are configured
using the Extinguishing Relay and Relay DIP switches on the ECU main board
(see Figure 8 below).
Figure 8: DIP switch locations on the ECU main board
Any two addresses may be used but the two addresses must be at least twenty
apart as security against short-term random noise interference.
The fire alarm control panel identifies the extinguishing relay address as an
extinguishing unit. The switches are numbered 1 to 7 and may be configured to
represent addresses from 1 to 127.
A switch represents a particular value when ON (an OFF switch represents 0).
To configure the address of a device, add the switch values for all the switches
which are ON. Note that the DIP switch number is not the DIP switch value – see
Figure 9 below.
Figure 9: DIP switch values and address example
ZP3-ECU Extinguishing Control Unit Installation and Commissioning Manual
19