DANGER
Overloading a branch circuit is potentially a fire hazard and a shock hazard under certain
conditions. To avoid these hazards, ensure that your system electrical requirements do not exceed
branch circuit protection requirements. Refer to the information that is provided with your device
for electrical specifications.
S014
CAUTION:
Hazardous voltage, current, and energy levels might be present. Only a qualified service technician is
authorized to remove the covers where the label is attached.
R009
CAUTION:
Removing components from the upper positions in the Enterprise Rack cabinet improves rack
stability during relocation. Follow these general guidelines whenever you relocate a populated rack
cabinet within a room or building:
• Reduce the weight of the rack cabinet by removing equipment starting at the top of the rack
cabinet. When possible, restore the rack cabinet to the configuration of the rack cabinet as you
received it. If this configuration is not known, you must do the following:
– Remove all devices in the 32 U position and above.
– Make sure that the heaviest devices are installed in the bottom of the rack cabinet.
– Make sure that there are no empty U positions between devices installed in the rack cabinet
below the 32 U position.
• If the rack cabinet that you are relocating is part of a suite of rack cabinets, detach the rack cabinet
from the suite.
• Inspect the route that you plan to take, to eliminate potential hazards.
• Make sure that the route that you choose can support the weight of the loaded rack cabinet. See
the documentation that comes with your rack cabinet for the weight of a loaded rack cabinet.
• Make sure that all door openings are at least 760 x 2030 mm (30 x 80 in.)
• Make sure that all devices, shelves, drawers, doors, and cables are secure.
• Make sure that the four leveling pads are raised to their highest positions.
• Make sure that no stabilizer bracket is installed on the rack cabinet.
144
ThinkSystem Heavy Duty Full Depth 48U Rack Cabinet User Guide