Instruments and Controls
14
Setup
parameter setting in the engine's control systems. Dif-
ferent menus appear under Customer parameter,
depending on whether Versatile or Gen set has been
selected from Set application. See below.
The parameters that can be set/selected (choice is
made with the SEL button) are:
Set application, setting Versatile or Gen set.
•
Depending on the selection made here, different
menus will appear under Customer parameter.
•
Unit, setting of units (metric or US imperial).
•
Language, setting the language used on the dis-
play. Choose between English, French, German
and Spanish.
•
Stop energized to, setting of external stop input.
Activated by Stop or Run.
Stop: The stop input must be connected to voltage
to stop the engine.
Run: The stop input must be connected to voltage
to run the engine.
•
Customer parameter, setting alarm limits. Refer to
Customer parameter / Versatile and Customer
parameter / Gen set.
Throttle input setting, setting of engine-speed
•
control and voltage limits. Refer to Throttle input
setting.
•
Display setting, setting the display. refer to Display
setting.
Customer parameter / Versatile
•
Idle engine speed - setting idle speed.
•
Preheat on ignition - activation of automatic pre-
heating. The engine control system senses if pre-
heating is needed and activates it directly at switch-
on.
•
Governor gradient (Nm/rpm) - setting of droop
level, when activated. For activation, refer to Gov-
ernor droop in the main menu.
•
Oil temp warning limit (°C) - setting alarm limit for
oil temperature.
•
Coolant temp warning limit (°C) - setting alarm
limit for coolant temperature.