MULTISPAN ELR-19N-M1 Installation Manuallines page 4

Earth leakage relay

Advertisement

MODBUS PARAMETER
Press
Key To Enter Into Modbus Parameter
+
SET
A D D R
0 0 1
Press
key
SET
B A U D
9 6 0 0
Press
key
SET
P A R 1
N O N E
Press
key
SET
D A T A
F L O T
Press
key
SET
R D F C
0 H 0 3
Press
key
SET
W D F C
O H 1 O
ENT
Press
RST
MODBUS
Salve Address :
Baudrate :
Parity :
Datatype :
Read Function Register :
Write Function Register :
Addresss
1 to 128
Baudrate
(4800,9600,19200)
Parity
(None,Even,Odd)
Datatype
(Float,Integer,Long)
Read Data Function
(0x03,0x04)
Write Data Function
(0x010,0x06)
key to save parameter & exit.
1 to 128
4800,9600,19200 bps
None,Even,Odd
Long, Float,Integer
0x03,0x04
0x10,0x06
Access
Sr.No
Parameter
Type
1
R
Relay 1 Status
Selection
ON
OFF
2
R
Leakage Value
3
R/W
Set Value
4
R/W
Delay Time
5
R/W
Hysterisis
R/W
Healthy condition
6
Relay mode
Selection
ON
OFF
Reset mode
R/W
7
Selection
Auto
Manual
Password Enb/Dis
R/W
8
Selection
Enable
Disable
9
R/W
Address
Baudrate
10
R/W
Selection
4800
9600
19200
Parity
11
Selection
R/W
None
Even
Odd
Data Type
12
Selection
R/W
Long
Float
Integer
R/W
Read Function
13
Selection
0x03
0x04
R/W
Write Function
14
Selection
0x06
0x010
Specifications are subject to change, since development is a continuous process,
So for more updated operating information and Support,
Please contact our Helpline: 9978991474/76/82 or
Email at
service@multispanindia.com
Register
Data Type
Integer Float &
long
0
0
Value
1
0
1
2
2
4
3
6
4
8
5
10
Value
0
1
6
12
Value
0
1
14
7
Value
0
1
8
16
9
18
Value
0
1
2
10
20
Value
0
1
2
11
22
Value
0
1
2
12
24
Value
0
1
13
26
Value
0
1
Ver:191201
Page 4