Earth to Neutral Relay
FEATURE
Earth to Neutral Voltage Monitoring In 1Ø - 2W, 3Ø-3W
And 3Ø-4W System
Auto/Manual Triping Reset Facility.
Trip Reset Via Front Key
TECNICAL SPECIFICATION
INPUT SPECIFICATION :
Input Voltage
0 To 10 V AC
Display Voltage Range
0.00 To 10.00 V AC
Resolution
0.01 V AC
DISPLAY & KEYS :
Upper: 4 Digit , 7 Seg. 0.56" Red
Display
Lower: 4 Digit , 7 Seg. 0.56"Green
Keys
SET, INC, DEC, ENT/RST
DIMENSION :
Size (mm)
96(H) X 96(W) X 52(D)
Panel Cutout
92(H) X 92(W)
OUTPUT SPECIFICATION :
Relay
1 Nos.
Relay Type
1 C/O (NO-C-NC)
Rating
10A,230V AC Resistive Load
AUXILIARY SUPPLY :
EN-19N
Supply Voltage
100 To 250 V AC
Power Consumption
4VA @ 230 VAC MAX
(VA Rating)
ENVIRONMENT CONDITION:
Operating Temp.
0°C to 55°C
UP to 95% RH
Relative Humidity
(non-condensing)
Protection Level
IP-65 (Front side) As per IS/IEC
(As per request)
60529 : 2001
MECHANICAL DIMENSION
Outline Dimension (mm)
EN 19N
1 8 3
Voltage
1 0 0 0
R
96
Set Value
Earth to Neutral Voltage Relay
ENT
SET
RST
52
96
3
TERMINAL CONNECTION
20
19
18
17
16
15
E
N
I/P
0 To 10V AC
Input: 0 To 10V AC
Range: 0.00 To 10.00V AC
~
100
250V AC
50/60 HZ
!
4VA
NO
C
NC
L
N
1
2
3
4
5
6
KEY OPERATION
FUNCTION
To Enter in Parameter Setting
To Reset the Relay Contact
Manually After Tripping
To set parameter value
To increment parameter value.
To decrement parameter value.
Set parameter to be save & exit.
Panel Cutout
Dimension (mm)
SAFETY PRECAUTION
!
92
All safety related codifications, symbols and instructions that
appear in this operating manual or on the equipment must be
92
strictly followed to ensure the safety of the operating personnel
as well as the instrument.
If all the equipment is not handled in a manner specified by
the manufacturer, it might impair the protection provided by the
equipment.
Read complete instructions prior to installation
and operation of the unit.
14
13
12
11
WARNING : Risk of electric shock.
MAINTENANCE
1. The equipment should be cleaned regularly to avoid blockage
www.multispanindia.com
of ventilating parts.
MadeinIndia
2. Clean the equipment with a clean soft cloth. Do not use
isopropyl alcohol or any other cleaning agent.
7
8
9
10
3. Fusible resistor must not be replaced by operator.
KEY PRESS
1. To prevent the risk of electric shock, power supply to the
equipment must be kept OFF while doing the wiring
OPERATION MODE
arrangement. Do not touch the terminals while power is
being supplied.
SET
2. To reduce electro magnetic interference, use wire with
adequate rating and twists of the same of equal size shall
ENT
For 2 sec
be made with shortest connection.
RST
3. Cable used for connection to power source, must have a
cross section of 1mm or greater. These wires should have
insulations capacity made of at least 1.5kV.
SET
4. When extending the thermocouple lead wires, always use
thermocouple compensation wires for wiring for the RTD
type, use a wiring material with a small lead resistance
(5 max per line) and no resistance differentials among
three wires should be present.
5. A better anti-noise effect can be expected by using
standard power supply cable for the instrument.
ENT
RST
1. This equipment, being built-in-type, normally becomes a
part of main control panel and in such case the terminals
do not remain accessible to the end user after installation
and internal wiring.
2. Do not allow pieces of metal, wire clippings, or fine metallic
fillings from installation to enter the product or else it may
lead to a safety hazard that may in turn endanger life or
cause electrical shock to the operator.
3. Circuit breaker or mains switch must be installed between
power source and supply terminal to facilitate power 'ON'
or 'OFF' function. However this mains switch or circuit
breaker must be installed at convenient place normally
accessible to the operator.
4. Use and store the instrument within the specified ambient
temperature and humidity ranges as mentioned in this
manual.
MECHANICAL INSTALLATION GUIDELINES
1. Prepare the panel cutout with proper dimensions as shown
above.
2. Fit the unit into the panel with the help of clamp given.
3. The equipment in its installed state must not come in close
proximity to any heating source, caustic vapors, oil steam,
or other unwanted process Byproducts.
4. Use the specified size of crimp terminal (M3.5 screws) to
wire the terminal block. Tightening the screws on the
terminal block using the tightening torque of the range of
1.2 N.m.
5. Do not connect anything to unused terminals.
WARNING GUIDELINES
WARNING : Risk of electric shock.
Ω
INSTALLATION GUIDELINES
Page -1
Need help?
Do you have a question about the EN-19N and is the answer not in the manual?
Questions and answers