3.10 FIRST IGNITION PARAMETER SETTING

During the first activation of the appliance, it is necessary to customise the following parameters, which concern the generator opera-
tion, the type of outdoor unit and the type of system connected to the appliance.
In the menu
Support / Heat pump / HP Type
you must ensure that the model set is 'MHP Mini'.
In the menu
Support / Heat pump / Powers
it is necessary to set "HP Model", which corresponds to the power of the outdoor unit.
In the menu
Support / Heat pump / Timers
You can customise the device's restart delay by modifying the parameter "Anti-cycle time" and, in the presence of delayed opening sys-
tems, you can modify the parameter "Req.delay time TA".
In the menu
Support / Heat pump / Pump
it is possible to modify the heat pump circulator speed by modifying the parameter "Max pump speed".
It is necessary to adjust the pump speed according to the appliance power, to improve the operating efficiency of the machine.
The heat pump is equipped with a sanitary electric resistance as standard.
The standard supplied electrical resistance is disabled as a precaution (it is necessary for the resistance to be activated only in the presence
of Domestic hot water / D.H.W. in the storage tank).
Therefore, it is necessary to enable the electrical resistance by modifying the following parameters.
Modifying the parameter
Integration / Enable DHW integr.
it is decided whether to activate only the heat pump or only the resistance or both to perform the DHW Mode.
Modifying the parameter
Integration / DHW integration mode.
it is decided whether to activate the heat pump and the resistance in an alternate or simultaneous manner.
Modifying the parameter
Integration / DHW wait time
it is decided how long to activate the heat pump and the electrical resistance or both together.
When the outdoor temperature is lower than:
Special parameters / Parameter 3
the electrical resistance activates automatically.
In case of simultaneous DHW (Domestic hot water) and system requests, the system alternates the two operating modes according to the
times set in the parameters:
Integration / Time preceding DHW
Integration / Pre-heating time