1.17 INDOOR UNIT START-UP (IGNITION)

After having installed the chiller lines on the outdoor unit, to commission the heat pump (the operations listed below must only be per-
formed by qualified personnel and in the presence of staff only):
1. Check connection to a 230V~50Hz power mains, correct L-N polarity and the earthing connection;
2. Switch the indoor unit on and check correct ignition;
3. Check the intervention of the main switch located upstream from the indoor unit and in the indoor unit.
4. Set the first ignition parameters (Par. 3.9).
The system must not be started up if even only one of the checks should be negative.
After installation, check for leaks. Toxic gas could be generated if the unit comes into contact with a source of
ignition, such as thermal fan, stove and cylinders. Make sure that only refrigerant recovery cylinders are used.
Apply the product data nameplate contained inside the warranty envelope, in an accessible and visible position.
Use the serial number on this plate for THERMAL/GSE practices.