6800
12.4.6 Normative values
Modbus
6900
12.4.7 Alarms
Modbus
7000
7010
7020
7030
7040
7100
7110
7120
7130
7140
7200
7210
7220
7230
7240
7300
7310
7320
7330
7340
F32
Airflow coefficient (allows to cal-
culate an airflow from the pres-
sure)
Register type
U8
Normative Value
Register type
BOOLEAN
Alarm 1 raised
F32
Channel 1 measured value
U8
Channel 1 measure status
I8
Channel 1 trend
U8
Channel 1 error reason
BOOLEAN
Alarm 2 raised
F32
Channel 2 measured value
U8
Channel 2 measure status
I8
Channel 2 trend
U8
Channel 2 error reason
BOOLEAN
Alarm 3 raised
F32
Channel 3 measured value
U8
Channel 3 measure status
I8
Channel 3 trend
U8
Channel 3 error reason
BOOLEAN
Alarm 4 raised
F32
Channel 4 measured value
U8
Channel 4 measure status
I8
Channel 4 trend
U8
Channel 4 error reason
Description
Description
From 0.1 to 9999.9.
Possibilities
Possibilities
In unit selected for the channel (cf
register 2000).
0: OK, 1: Out of range, 2: Error, 3:
Heating
0: down, 1: equal, 2: up, 3: unavail-
able
0: none, 1: internal, 2: not configured,
3: measure, 4: unplugged probe,
5: invalid probe, 6: probe to update
In unit selected for the channel (cf
register 2100).
0: OK, 1: Out of range, 2: Error, 3:
Heating
0: down, 1: equal, 2: up, 3: unavail-
able
0: none, 1: internal, 2: not configured,
3: measure, 4: unplugged probe,
5: invalid probe, 6: probe to update
In unit selected for the channel (cf
register 2200).
0: OK, 1: Out of range, 2: Error, 3:
Heating
0: down, 1: equal, 2: up, 3: unavail-
able
0: none, 1: internal, 2: not configured,
3: measure, 4: unplugged probe,
5: invalid probe, 6: probe to update
In unit selected for the channel (cf
register 2200).
0: Ok, 1: Out of range, 2: Error, 3:
Heating
0: down, 1: equal, 2: up, 3: not avail-
able
0: none, 1: internal, 2: not configured,
3: measure, 4: unplugged probe,
5: invalid probe, 6: probe to update