Perform An Output Diagnostic - sauermann Si-C320 User Manual

Multifunction transmitter
Hide thumbs Also See for Si-C320:
Table of Contents

Advertisement

"I/O Configurations" menu is displayed.
• Tap "Outputs".
• Tap "Analog Outputs".
• Tap the desired output (Output 1, 2, 3 or 4 depending on the number of the previously configured channel).
Features of the output are displayed.
• Tap
on the top right of the screen to activate the output
• Tap "Output type".
• Select the output type: 0-5 V, 0-10 V, 0-20 mA or 4-20 mA then tap the back arrow on the top left of the screen.
• Tap "High range".
• Define the high range value for the output then tap the back arrow on the top left of the screen.
• Tap "Low range".
• Define the low range value for the output then tap the back arrow on the top left of the screen.

9.2.2 Perform an output diagnostic

This function allows to check on a measurement device (multimeter, regulator or automate) the proper functioning
of the outputs. The transmitter will generate a voltage (between 0 and 10 V) or a current (between 0 and 20 mA)
according to the setting of the type of output.
• For a 0-10 V output signal, the transmitter will generate 0 – 5 or 10 V.
• For a 0-5 V output signal, the transmitter will generate 0 – 2.5 or 5 V.
• For a 4-20 mA output signal, the transmitter will generate 4 – 12 or 20 mA.
• For a 0-20 mA output signal, the transmitter will generate 0 – 10 or 20 mA.
Before carrying out the output diagnostics, all connections and configurations of the transmitter
must be enabled, to avoid any damage on the transmitter and the measurement device.
• Select a channel for the outputs diagnostic.
OUT1, OUT2, OUT3 or OUT4 indicated on the electronic board above the terminal blocks.
• Connect a measurement device on the output 1, 2, 3 or 4.
Once the connection to the measurement device is complete, the output diagnostic on several check points can be
performed:
"I/O Configurations" menu is displayed.
• Tap "Outputs".
• Tap "Analog Outputs".
• Tap "Diagnostic" line.
• Tap the required value.
The values proposed will depend on the type of output previously selected. For example, if the output type
is 4-20 mA, proposed values will be 4 mA, 12 mA and 20 mA.
18
Set inputs and outputs