Set Inputs And Outputs; Set The Measurement Channels; Set The Outputs; Set The Analog Outputs - sauermann Si-C320 User Manual

Multifunction transmitter
Hide thumbs Also See for Si-C320:
Table of Contents

Advertisement

"I/O Configurations" menu allows to set the following items:
• Channels: activate and set the probes and modules connected to the transmitter
• Outputs: activate and set outputs corresponding to the channels
• Probes and Modules: define normative values according to probes and modules connected to the transmitter and
define some parameters linked to probes and modules
• Alarms: activate and set alarm features
• Autozero: activate and set the autozero interval
To access this menu:
• Tap
on the measurement screen.
• Tap the security code.
Default security code is 0101. This code can be modified in "Security/Connectivity" menu. See chapter 9.2
on page 25.
• Tap "I/O Configurations".

9.1 Set the measurement channels

At least one probe or one differential pressure module must be connected to the transmitter.
"I/O Configurations" menu is displayed.
• Tap "Channels".
• Tap the desired channel number (Channel 1, 2, 3 or 4).
Features of the channel are displayed.
• Tap "PROBE 1", "PROBE 2" or "MODULE" according to the required attribution for the channel.
"Measures" becomes available.
• Tap "Measures".
• Select the required parameter then tap the back arrow on the top left of the screen.
• Tap "Units".
• Select the required measurement unit then tap the back arrow on the top left of the screen.
The channel is automatically activated (toggle switch is on).
• If required, enter a coefficient and an offset to the channel.
• Tap the back arrow on the top left of the screen until measurement screen is displayed.
"Values measured by the probe or the module are displayed.
Special case: two units are available for the VOC probe: ppb and ppm CO
selected, the transmitter will take 15 minutes to display the first measurements (pre-heating
phase).
The channel name can be changed:
• Tap
next to the channel name to edit it.
• Enter a name. Maximum characters: 13.
• Tap OK to validate.

9.2 Set the outputs

Two types of outputs are available: analog outputs and digital outputs

9.2.1 Set the analog outputs

At least one measurement channel must be configured.
If no channel has been configured, no analog output will be delivered.

Set inputs and outputs

9. Set inputs and outputs
equivalent. If ppm is
2
17