7.1.2 Refrigerant piping insulation
7.2 Connecting the refrigerant piping
7.2.1 About connecting the refrigerant piping
7.2.2 Precautions when connecting the refrigerant piping
FTXP20~35M5V1B9
Split system air conditioners
4P519439-7S – 2021.12
▪
Use polyethylene foam as insulation material:
-
with a heat transfer rate between 0.041 and 0.052 W/mK (0.035 and
0.045 kcal/mh°C)
-
with a heat resistance of at least 120°C
▪
Insulation thickness
Pipe outer diameter (Ø
6.4 mm (1/4")
9.5 mm (3/8")
12.7 mm (1/2")
Ø
Ø
i
i
Ø
Ø
p
p
t
If the temperature is higher than 30°C and the humidity is higher than RH 80%, the
thickness of the insulation materials should be at least 20 mm to prevent
condensation on the surface of the insulation.
Before connecting the refrigerant piping
Make sure the outdoor and indoor unit are mounted.
Typical workflow
Connecting the refrigerant piping involves:
▪
Connecting the refrigerant piping to the indoor unit
▪
Connecting the refrigerant piping to the outdoor unit
▪
Insulating the refrigerant piping
▪
Keeping in mind the guidelines for:
-
Pipe bending
-
Flaring pipe ends
-
Using the stop valves
INFORMATION
Also read the precautions and requirements in the following chapters:
▪
General safety precautions
▪
Preparation
DANGER: RISK OF BURNING/SCALDING
) Insulation inner diameter
p
(Ø
)
i
8~10 mm
12~15 mm
14~16 mm
7
Piping installation
|
Insulation thickness (t)
≥10 mm
≥13 mm
≥13 mm
Installer reference guide