Piping Installation; Preparing Refrigerant Piping; Refrigerant Piping Requirements - Daikin FTXP25M5V1B9 Installer's Reference Manual

Split system
Hide thumbs Also See for FTXP25M5V1B9:
Table of Contents

Advertisement

7
|

Piping installation

7 Piping installation
In this chapter

7.1 Preparing refrigerant piping

7.1.1 Refrigerant piping requirements

Refrigerant piping diameter
Refrigerant piping material
Installer reference guide
28
7.1
Preparing refrigerant piping ...................................................................................................................................................
7.1.1
Refrigerant piping requirements ...........................................................................................................................
7.1.2
Refrigerant piping insulation..................................................................................................................................
7.2
Connecting the refrigerant piping..........................................................................................................................................
7.2.1
About connecting the refrigerant piping...............................................................................................................
7.2.2
Precautions when connecting the refrigerant piping............................................................................................
7.2.3
Guidelines when connecting the refrigerant piping..............................................................................................
7.2.4
Pipe bending guidelines .........................................................................................................................................
7.2.5
To flare the pipe end..............................................................................................................................................
7.2.6
To connect the refrigerant piping to the indoor unit............................................................................................
INFORMATION
Also read the precautions and requirements in the
4
precautions" [
NOTICE
The piping and other pressure-containing parts shall be suitable for refrigerant. Use
phosphoric acid deoxidised seamless copper for refrigerant.
Foreign materials inside pipes (including oils for fabrication) must be
≤30 mg/10 m.
Use the same diameters as the connections on the outdoor units:
Class
20~35
50~71
Piping material: Phosphoric acid deoxidised seamless copper.
Flare connections: Only use annealed material.
Piping temper grade and thickness:
Outer diameter (Ø)
6.4 mm (1/4")
9.5 mm (3/8")
12.7 mm (1/2")
(a)
Depending on the applicable legislation and the maximum working pressure of the unit
(see "PS High" on the unit name plate), larger piping thickness might be required.
 5].
L1 liquid piping
Ø6.4
Ø6.4
Temper grade
Annealed (O)
"2  General safety
L1 gas piping
Ø9.5
Ø12.7
(a)
Thickness (t)
≥0.8 mm
FTXP20~35M5V1B9
Split system air conditioners
4P519439-7S - 2021.12
28
28
29
29
29
29
30
31
31
32
Ø
t

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ftxp20m5v1b9Ftxp35m5v1b9

Table of Contents