Refrigerant type,
Full-Feature units
(1)
Refrigerant quantity,
Full-Feature units
Refrigerant quantity,
Full-Feature units
(1)
Cooling water consumpation
( at water inlet temperature
0
below 35
C
temperature rise of 15
water cooled units
Cooling water consumpation
( at water inlet temperature
between 35 and 40
temperature rise of 10
water cooled units
Oil capacity,air-cooled units
Oil capacity,water-cooled
units
Sound pressure level,
Workplace and workplace
Full-Feature (according to
ISO 2151 (2004))
136
Units
7.5 bar
R410A
kg
1.3
kg
1.00
l/min
39
0
C ),
l/min
59
0
C and
0
C ),
l
21
l
22
dB(A)
66
8 bar
10 bar
R410A
1.3
1.3
0.97
0.97
39
39
59
59
21
21
22
22
66
66
Instruction book
13 bar
R410A
1.3
0.97
39
59
21
22
65
9096 3321 00