Technical Data; Electrical Data - Riello 20072969 Installation, Use And Maintenance Instructions

Forced draught gas burners
Table of Contents

Advertisement

4.3

Technical data

Model
Type
Power
(1)
Output
(1)
Fuels
Gas pressure at max. output
Gas: G20/G25
Operation
(3)
Standard applications
Ambient temperature
Combustion air temperature
Noise levels
Sound pressure
(4)
Sound power
Weight
Reference conditions: Ambient temperature 20°C - Gas temperature 15°C - Barometric pressure 1013 mbar - Altitude 0 m a.s.l.
(1)
Pressure on the socket 5) (Fig. 4) with zero pressure in the combustion chamber and at maximum burner output.
(2)
The burner is factory set for FS1 operation (1 stop every 24 hours); it can be converted to FS2 operation (continuous - 1 stop every 72 hours), by
(3)
changing the parameters using the AZL Display menu.
Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum rated output. The sound
(4)
power is measured with the "Free Field" method, as per EN 15036, and according to an "Accuracy: Category 3" measuring accuracy, as set out in
EN ISO 3746.
4.4

Electrical data

Model
Electrical supply
Fan motor IE2
Ignition transformer
Absorbed electrical power
Protection level
Model
Electrical supply
Fan motor IE3
Ignition transformer
Absorbed electrical power
Protection level
20087244
Technical description of the burner
min - max
kW
-
(2)
mbar
°C
°C max
dB(A)
Kg
rpm
Hz
V
kW
A
V1 - V2
I1 - I2
kW max
rpm
Hz
V
kW
A
V1 - V2
I1 - I2
kW max
RS 1000/EV BLU
1133 T2
1100/4000 - 10100
Natural gas: G20 (methane gas) - G21 - G22 - G23 - G25
64.5/92.7
Intermittent (min. 1 stop in 24 hours)
Modulating
Boilers: water, steam, diathermic oil
85
99
460
RS 1000/EV BLU
3N ~ 400V +/-10% 50Hz
2964
50
400/690
22
38.6/22.3
24
RS 1000/EV BLU
3N ~ 400V +/-10% 50 Hz
2880
50
400/690
22
38.2/22.3
24
8
GB
RS 1200/EV BLU
1134 T2
1500/5500 - 11100
80.5/114
0 - 50
60
89.3
99.7
500
RS 1200/EV BLU
2920
50
400/690
25
44.1 - 25.5
230 V - 2 x 5 kV
1,9 A - 35 mA
27
IP 54
RS 1200/EV BLU
2880
50
400/690
25
43.4/25.1
230 V - 2 x 5 kV
1,9 A - 35 mA
27
IP 54
Tab. B
Tab. C
Tab. D

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rs 1200/ev bluRs 1000/ev blu200729701133 t21134 t2

Table of Contents