1MRK 506 377-UEN Rev. K
Section 8
8.1

Overview

The rear optical Ethernet ports are used for:
process bus (IEC/UCA 61850-9-2LE) communication
substation bus (IEC 61850-8-1) communication
8.2

Setting the station communication

To enable IEC 61850 communication, the corresponding ports must be activated. The rear access
points can be used for IEC 61850-8-1 and IEC/UCA 61850-9-2LE communication. IEC 61850-8-1
redundant communication requires the use of two Ethernet ports, when it is activated for Ethernet
port the next immediate port is selected as the second Ethernet port and will become hidden.
To enable IEC 61850 station communication:
1.
Activate IEC 61850-8-1 (substation bus) communication.
Navigate to: Main menu /Configuration/Communication /Station communication/
IEC61850–8–1 /IEC61850–8–1:1
2.
Enable operation for Access Point 1 and 3 in the Ethernet configuration tool (ECT) in PCM600.
3.
Enable redundant communication for Acess point 1 using ECT.
4.
Enable IEC/UCA 61850-9-2LE (process bus) communication for Access point 3 by connecting
it to a Merging unit in the Merging units tab in ECT.
There are no settings needed for the IEC/UCA 61850-9-2LE communication in the local HMI branch
Station communication . Make sure that the optical fibers are connected correctly. Communication
is enabled whenever the merging unit starts sending data.
8.3

Verifying the communication

To verify that the communication is working a test/analyzing tool, for example ITT600, can be used.
Verifying redundant IEC 61850-8-1 communication
Ensure that the IED receives IEC 61850-8-1 data on the selected Ethernet ports. Browse in the local
HMI to Main menu /Diagnostics /Communication /Ethernet status /Access point /
APStatusRedundant /RCHLCCH:1 and check that ChARedStatus and ChBRedStatus are shown
as Ok. This is only applicable if redundant communication is used. Remove the optical connection to
Railway application RER670
Commissioning manual
Establishing connection and
verifying the IEC 61850
communication
When configuring RER670 for 9-2LE streams in a 16,7Hz system, the IED shall be
set to 16,7Hz and the MU to 50Hz (4kHz sampling).
In this example access points 1, 2 and 3 are used.
© 2017 - 2021 Hitachi Power Grids. All rights reserved

Establishing connection and verifying the IEC 61850 communication

Section 8
SEMOD172103-4 v9
SEMOD172108-3 v14
SEMOD172108-24 v12
53