ATTACH RS-485 COMMUNICATION WIRES TO THE MS/TP SUBNET PORT

Wiring the
RS-485
configuration. One end of the network will be connected to the Fieldbus of the Network-level controller or
BACnet®
router. At the other end of the network, the last device must be "terminated" by either installing a
100 Ω ... 120 Ω resistor or, if the last device is a MATRIX-2, users can switch the
switch (located beside the
The shield (screen) must be carried through the entire network, and must be grounded at one point on the
network as shown below:
Network-level Controller or
Router
Termination
Shield connected at end
switch set to
of network only
Note:
If the
RS-485
network is wired to an eSC, then the shield will be grounded at the eSC.
©ABB 2023 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
network involves connecting the
MS/TP
port) towards the
Network Segment
MATRIX-2
end
Network
Shield continuous
throughout the
OFF
network
Cylon® MATRIX-2 Series |
(95) and
(96) terminals in a daisy-chained
A+
B-
icon. This will effectively terminate the network.
- - - - - -
Network cable
Termination switch
segment daisy-chained
set to ON at end of
to next device
Installation
MS/TP
Subnet terminator
MATRIX-2
Network end
Network
Shield connected to
earth at one end of
network
network only