1MRK 506 377-UEN Rev. K
Table 38:
Headline
Incorrect setting of SyncLostMode
Sampled value substituted
Time diff: IED vs Sampled value
Frequency diff: IED vs Sampled value
Wrong cycle time for PMU report
PMU not connected to 3ph output
Invalid value set for PMU Parameters
Invalid phase angle reference
GOOSE is configured on a disabled port
LDCM not running the application image
LDCM rate (2M) is not supported
Table continues on next page
Railway application RER670
Commissioning manual
Hint menu
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Explanation
There are two explanations possible:
SyncLostMode is set to Block, no time source is
configured to achieve the required accuracy. Unless a
high accuracy time source is selected, the function
dependent on high time accuracy will be blocked.
SyncLostMode is set to BlockOnLostUTC, but there is no
UTC capable synch source (GPS, IRIG-B) used. Unless
a UTC capable time source is selected, the function
dependent on high time accuracy will be blocked.
<Access Point><Hardware Module Identifier><svID>
Where the Hardware Module Identifier is the same as
given in PCM600, e.g. AP1: MU1_9201 svID: <Hitachi
Power grids_MU0101>
<Access Point><Hardware Module Identifier><svID>
Where the Hardware Module Identifier is the same as
given in PCM600, e.g. AP1: MU1_9201 svID: <Hitachi
Power grids_MU0101>
<Access Point><Hardware Module Identifier><svID>
Where the Hardware Module Identifier is the same as
given in PCM600, e.g. AP1: MU1_9201 svID: <Hitachi
Power grids_MU0101>
Wrong cycle time on SMAI or 3PHSUM block connected
to Phasor Report block. The SMAI or 3PHSUM block
should have same cycle time as that of Phasor Report.
The PMU phasor report input(s) must be connected to
the 3ph output of SMAI or 3PHSUM.
There are two possible error conditions:
Check if the following parameters are set correctly on
PMUREPORT:1 ReportRate or SvcClass or parameter
PRIMVAL:1.FrequencySel is not set as 50Hz / 60Hz.
Check if the following parameters are set correctly on
PMUREPORT:1 ReportRate or SvcClass or RptTimetag
or parameter PRIMVAL:1.FrequencySel is not set as
50Hz / 60Hz.
The selected PhaseAngleRef corresponds to an analog
channel that is not configured. Configure a valid
reference channel.
At least one of the access points configured for GOOSE
is disabled. The port can be disabled either through
changing the access point operation to off or by
unchecking the GOOSE protocol from the access point
in the Ethernet configuration in PCM600 or LHMI.
Enable GOOSE on access points:
<Access Points>, can be any of these: AP_FRONT,
AP_1, AP_2, AP_3, AP_4, AP_5, AP_6,AP_7, AP_8
LDCM in <slot number> is running the factory image
instead of the application image. The factory image is
older than the required FW version and does not contain
the latest updates and fixes.
Reboot the IED. If the problem persists, update the
LDCM firmware or replace the board.
The <firmware version> does not support 2M mode. Set
the LDCM to 64k bit mode.
Section 12
Troubleshooting
167