ELECTRICAL CONNECTIONS
Any cable connection or hook-up to the grid must be carried out by qualified, informed and trained personnel, directly coor-
dinated and authorized by Technical Service. Always check in advance that the system electrical interlock is fitted with a
safety circuit breaker.The installation must be built in accordance with the regulations in force and comply with basic safety
rules.
See the wiring diagram for more information.
WARNING: It is possible that some components are still live despite being disconnected from the mains and can cause
electric shocks.
WARNING: ! before executing the electrical connections, pay attention to turn the plant's switch to OFF and be sure that the
burner's main switch is in 0 position (OFF) too. Read carefully the chapter "WARNINGS", and the "Electrical connections"
section.
Note on electrical supply
WARNING:
The implant must have / in the implant there must be:
Have earthing connected to the burner; always check the connection, functionality and health and safety compliance of
the earthing cable beforehand. If in doubt, request a thorough check by qualified technical personnel.
Do not use foreign masses (e.g. fuel lines, metal structures...) to connect the burner to earth.
When connecting the power wires to the burner's MA terminal block, ensure that the earth wire is longer than the phase
and neutral wires.
Do not reverse the phase and neutral connections.
Provide an omnipolar switch-disconnector and a residual current circuit breaker, circuit breaker or fuses on the electrical
supply line to the burner.
Always check the protection of the mains system against overcurrents and electromagnetic interference as a preventive
measure.
Check that the voltage for which the system and the burner motors are designed corresponds to the mains voltage (+/-
10%).
Before carrying out any work on the machine's electrical panel, open the system's omnipolar switch disconnector and
turn the switch on the burner's electrical panel OFF.
In any case:
Provide adequately protected and safe mains supply and mains/burner tracing cables, with flame-proof electric cable of a
cross-section suitable for the installed power;
Absolutely avoid the use of extension cords, adapters or power strips;
In the case where the power supply of the AUXILIARIES of the phase-phase burner (without a neutral), for the flame detection it is ne-
cessary to connect the RC circuit Siemens between the terminal 2 (terminal X3-04-4 in case of LMV2x, LMV3x, LMV5x, LME7x) of the
base and the earth terminal, RC466890660. For LMV5 control box, please refer to the clabeling recommendations avaible on the Sie-
mens CD attached to the burner
Key
C - Capacitor (22 nF , 250 V)
LME / LMV - Siemens control box
R - Resistor (1 MΩ)
M: Terminal 2 (LGB, LME), Terminal X3-04-4 ( LMV2x, LMV3x,
LMV5, LME7x)
RC466890660 - RC Siemens filter
PART III: INSTALLATION
LMV2/3... - LMV5...
M
22