Download Print this page

Carrier 38VT 188CTST Series Installation Manual page 15

Hide thumbs Also See for 38VT 188CTST Series:

Advertisement

Capacity code of indoor and outdoor units
For the indoor unit, the capacity code is decided at each capacity rank. (Table 1)
The capacity codes of the outdoor units are decided at each capacity rank. The maximum number of connectable
indoor units and the total value of capacity codes of the indoor units are also decided. (Table 2-1, Table 2-2)
NOTE
Compared with the capacity code of the outdoor unit, the total value of capacity codes of the connectable
indoor units differs based on the height difference between the indoor units.
When the height difference between the indoor units is 15 m or less: Up to 200% of the capacity code
(Equivalent to HP) of the outdoor unit.
When the height difference between the indoor units is over 15 m: Up to 105% of the capacity code.
40VU
If
S is include in the system, total indoor capacity code must be between 50% and 105% of
outdoor unit capacity.
If the system diversity is more than 135%, check the maximum number of indoor unit connections in table 2-1,
2-2, and then turn on DIP switch 3 of SW103 on the interface P.C. boards.
Table 1
Capacity code
Indoor unit
Equivalent to
capacity rank
Equivalent to HP
capacity
007
0.8
2.2
008
0.9
2.5
009
1
2.8
010
1.1
3.2
012
1.25
3.6
014
1.5
4
015
1.7
4.5
017
1.85
5
018
2
5.6
020
2.25
6.3
024
2.5
7.1
027
3
8.0
030
3.2
9.0
036
4
11.2
048
5
14.0
056
6
16.0
072
8
22.4
096
10
28.0
112
12
33.5
128
14
40.0
144
16
45.0
192
20
56.0
Table 2-1 [Diversity 135%]
Capacity code
Model Name
Equivalent
[Standard]
to HP
38VT0081
8
38VT0101
10
38VT0121
12
38VT0141
(014A
)
14
38VT0161
16
38VT018
1
18
38VT0201
20
38VT0221
22
38VT0241
24
38VT0261
26
38VT2811
28
38VT3011
30
38VT3211
32
38VT3411
34
38VT3611
36
38VT3811
38
38VT4011
40
38VT4211
42
38VT4411
44
38VT4611
46
38VT4811
48
38VT5011
50
38VT5211
52
38VT5411
54
38VT5611
56
38VT5811
58
38VT6011
60
38VT6211
62
38VT6411
64
38VT6611
66
38VT6811
68
38VT7011
70
38VT7211
72
38VT7411
74
38VT7611
76
38VT7811
78
38VT8011
80
38VT8211
82
38VT8411
84
38VT8611
86
38VT8811
88
38VT9011
90
38VT9211
92
38VT9411
94
38VT9611
96
38VT9811
98
38VT10011
100
– 14 –
Max. No.
Total
of indoor
capacity of
Equivalent
units
indoor units
to capacity
22.4
13
30.2
28.0
16
37.8
33.5
20
45.2
40.0
23
54.0
45.0
27
60.7
50.4
30
68.0
56.0
33
75.6
61.5
37
83.0
67.0
40
90.4
73.0
43
98.5
80.0
47
108.0
83.9
50
113.2
89.5
54
120.8
95.0
57
128.2
100.5
60
135.6
106.5
64
143.7
113.0
67
152.5
117.5
70
158.6
123.0
71
166.0
128.5
72
173.4
134.0
73
180.9
140.0
74
189.0
146.0
75
197.1
151.0
76
203.8
156.5
77
211.2
162.0
78
218.7
167.5
79
226.1
174.0
80
234.9
179.5
81
242.3
184.5
82
249.0
190.0
83
256.5
195.5
84
263.9
201.0
85
271.3
207.0
86
279.4
213.0
87
287.5
219.0
88
295.6
223.5
90
301.7
229.0
92
309.1
234.5
94
316.5
240.5
96
324.6
246.5
98
332.7
252.5
100
340.8
259.0
102
349.6
262.5
104
354.3
268.0
106
361.8
274.5
108
370.5
280.0
110
378.0
Diversity
(%)
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
135%
EN
135%
135%
135%
EN
135%
135%
135%
EN
135%
135%
135%
ID
135%
135%

Advertisement

loading

This manual is also suitable for:

38vt 188ctstz series