- Code on display
- Error message
Name of Alarm and Cause
- Signal
- E005
Communication error inside the inverter:
- Comm.Error
The alarm occurs when there are communication prob-
-
Alarm LED
lems between the control devices inside the inverter.
Output overcurrent:
- E006
The alarm occurs when the inverter's output current
- Output OC
exceeds the inverter's threshold for maximum output
-
Alarm LED
current.
- E007
Saturation recorded on the IGBT components:
- IGBT Sat
The alarm occurs when one of the inverter's active de-
-
Alarm LED
vices is in a saturated state.
- E009
Error inside the inverter:
- Internal error
Error inside the inverter
-
Alarm LED
Low "Bulk" voltage (DC-DC circuit):
The alarm may be triggered by causes external to the
- E010
inverter: a reduced input voltage on the inverter (just
- Bulk Low
above the activation voltage) but which is not accom-
-
Alarm LED
panied by a sufficient availability of power from the
photovoltaic generator (typical condition of the stages
with limited irradiation)
- E011
Long wait for "Booster" regime to start:
- Ramp Fail
Error internal to inverter relating to start up time for DC-
-
Alarm LED
DC circuit regime (Booster)
Error in the "Booster" circuit (DC-DC side) record-
- E012
ed by the "Inverter" circuit (DC-AC side):
- DcDc Fail
Error internal to inverter relating to operation of the DC-
-
Alarm LED
DC circuit regime (Booster)
Incorrect configuration of inputs (set in parallel
rather than independent):
- E013
The alarm is generated solely when the inverter is con-
- Wrong Mode
figured with parallel inputs. In this particular configu-
-
Alarm LED
ration the inverter checks the input voltage of each of
the two channels and if the two voltages differ by more
than 20Vdc, the alarm is raised .
Excessive temperature inside the inverter:
External temperature over 60°C. This parameter also
- E014
depends on the power which the inverter must supply
- Over Temp.
since the measurement of temperatures is done inter-
-
Alarm LED
nally and is influenced by the heat dissipated by the
components of the inverter itself
- E015
Fault recorded on the "Bulk" capacitor:
- Bulk Cap Fail
Error inside the inverter relating to a problem in the bulk
-
Alarm LED
capacitors.
Error in the "Inverter" circuit (DC-AC side) record-
- E016
ed by the "Booster" circuit (DC-DC side):
- Inverter Fail
The alarm is generated when a problem is recorded in
-
Alarm LED
the inverter circuit (DC/AC)
Long wait for "Inverter" regime to start up:
Error internal to inverter relating to start-up time for the
DC-AC circuit regime (Inverter)
- E017
• The alarm may be triggered by causes external to
- Start Timeout
the inverter: a reduced input voltage on the inverter
-
Alarm LED
(just above the activation voltage) but which is not ac-
companied by a sufficient availability of power from the
photovoltaic generator (typical condition of the stages
with limited irradiation)
Solution
• Error inside the inverter and cannot be checked externally.
- If the problem (once the inverter has been switched off and
back on) persists, contact customer assistance.
• Error inside the inverter and cannot be checked externally.
- If the problem (once the inverter has been switched off and
back on) persists, contact customer assistance.
Once the error occurs, the inverter tries to return to normal op-
eration.
- Should the error occur sporadically, it may be caused by a
brusque transition of the grid voltage or of the input voltage, but
is not due to a malfunction by the inverter.
- If the error is connected to an internal breakdown, it will con-
tinue to appear and so it is necessary to contact customer as-
sistance.
• Error inside the inverter and cannot be checked externally.
- If the problem (once the inverter has been switched off and
back on) persists, contact customer assistance.
- If the error signal occurs sporadically, it may be due to causes
external to the inverter (limited irradiation and so limited power
availability from the PV generator).
- If the problem occurs systematically also in conditions of high
irradiation and with input voltage which is significantly higher
than the activation voltage, contact customer assistance.
• Error inside the inverter and cannot be checked externally.
- If the problem (once the inverter has been switched off and
back on) persists, contact customer assistance.
• Error inside the inverter and cannot be checked externally.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
• Check that the setting of the "IN MODE" switch is specifically
set to "PAR" and that the bridges between the two input chan-
nels have been included.
- If the configuration of the inverter is correct, check that the
input strings have the usual number of standard panels of the
usual brand and with the same inclination/orientation.
- If both the configuration of the inverter and the characteristics
of the PV generator conform with the specifications, contact
customer assistance.
• Check that the inverter is not exposed to direct sunlight. Wait
for the temperatures to which the inverter is exposed to return
to the operating range and for the inverter to cool down.
- If the problem (once the ambient temperature has returned to
the range) persists, contact customer assistance. Remember
to wait the time needed to allow the inverter to cool down
• Error inside the inverter and cannot be checked externally.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
• Error inside the inverter and cannot be checked externally.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
- If the error signal occurs sporadically, it may be due to causes
external to the inverter (limited irradiation and so limited power
availability from the PV generator).
- If the problem occurs systematically also in conditions of high
irradiation and with input voltage which is significantly higher
than the activation voltage, contact customer assistance.
- 163 -