Self-Diagnostic Codes
When a self-diagnostic code is displayed on the LCD, the unit stops operation, relay contact RL07
for terminal OS-1 and OS2 is closed.
CODE
CONDITION
Cooling function failure
occurs 3 times and
CF
following condition
continues for 15 minutes
RTS - CTS1 < 9 °F (5 °C)
E1
RTS thermistor failure
E3
CTS1 thermistor failure
POSSIBLE CAUSE
Insufficient refrigerant or
refrigerant leak
Defective compressor
Loose RTS thermistor
connection
Defective RTS thermistor
(short or open circuit)
Loose CTS1 thermistor
connection
Defective CTS1 thermistor
(short or open circuit)
17
SOLUTION
Repair leak and add refrigerant based
on the weight listed on specifications or
nameplate
1. Replace compressor
2. Press CLEAR button to reset
Reconnect thermistor
Replace thermistor
Reconnect thermistor
Replace thermistor