Technical Specifications
Electronic Features
1
Cooling Capacity *
Electrical Characteristics
Fans: Motor Output
Evaporator
Condenser
Refrigerant Circuit
Refrigerant
Power Cord
Condensate Pump
ITEM
Control
Total Capacity
Power Requirement
Total Power Consumption *
Current Consumption *
Starting Current
Recommended Fuse Size
Min. - Max. Voltage
Energy Efficiency Ratio (EER)
Evaporator
Condenser
Fan Type
Max. Air Flow - high/mid/low
Max. External Static Pressure
Fan Type
Max. Air Flow - high/low
Max. External Static Pressure
Compressor Type
Compressor Motor Rated Output
Evaporator
Condenser
Refrigerant Control
Max. Allowable Pressure
- high/low
Type
Amount
NEMA Plug Configuration
Gauge
Length
10
SPECIFICATIONS
460V, 3 Phase, 60Hz
1
1
0.3 kW x 2 motors
1770/1710/1650 CFM
Hermetic Scroll
12 AWG (4-core)
1/30 HP, 230V, 0.5 amps, 75 W
Discharge Φ3/8 in
Programmable
60,000 Btu/h
6.6 kW
12.2 amps
52 amps
20 amps
440 -480
9.1
0.56 kW
Centrifugal
0.9 IWG
Centrifugal
2400 CFM
0.85 IWG
3.45 kW
Plate Fin
Plate Fin
Capillary Tube
820/384 PSIG
R-410A
3.97 lb (1.8 kg)
L16-20
6 ft