SUN600-(5KTL, 6KTL)-L0
User Manual
Alarm
Alarm Name
ID
2003
DC Arc Fault
2011
String Reversed
2021
AFCI Check
Failure
2032
Grid Failure
Issue 04 (2023-02-17)
Alarm
Possible Causes
Severity
Major
The PV string power cables
arc or are in poor contact.
● Cause ID 1 = PV1
● Cause ID 2 = PV2
Major
The PV string is reversely
connected.
Cause ID = 1, 2
● 1: PV1 is reversely
connected.
● 2: PV2 is reversely
connected.
Major
The AFCI check fails.
Cause ID = 1, 2
● 1: The AFCI check circuit
is abnormal.
● 2: The AFCI circuit is
faulty.
Major
Cause ID = 1
● The power grid
experiences an outage.
● The AC circuit is
disconnected or the AC
circuit breaker is OFF.
Copyright © Huawei Technologies Co., Ltd.
8 System Maintenance
Troubleshooting
Check whether the string
cables arc or are in poor
contact.
Check whether the PV
string is reversely
connected to the inverter. If
yes, wait until the PV string
current decreases below 0.5
A, set DC switch to OFF,
and adjust the PV string
polarity.
Turn off the AC output
switch and DC input switch,
and then turn them on
after 5 minutes. If the fault
persists, contact your
dealer.
1. Check the AC voltage.
2. Check whether the AC
circuit is disconnected or
the AC circuit breaker is
OFF.
79