SUN600-(5KTL, 6KTL)-L0
User Manual
Before performing
Step 2 Insert the positive and negative connectors into corresponding DC input terminals
on the inverter.
After the positive and negative connectors snap into place, pull the DC input
power cables back to ensure that they are connected securely.
Figure 5-15 Connecting DC input power cables
Issue 04 (2023-02-17)
NO TE
Use a multimeter to measure the voltage at the DC position. The multimeter must have a
DC voltage range of at least 600 V. If the voltage is a negative value, the DC input polarity
is incorrect and needs correction. If the voltage is greater than 600 V, too many PV modules
are configured to the same string. Remove some PV modules.
WARNING
Step
NO TICE
Copyright © Huawei Technologies Co., Ltd.
2, ensure that the DC switch is set to OFF.
5 Electrical Connection
50