Huawei SUN600-5KTL-L0 User Manual page 71

Hide thumbs Also See for SUN600-5KTL-L0:
Table of Contents

Advertisement

SUN600-(5KTL, 6KTL)-L0
User Manual
Figure 7-6 Grid-tied point control
Table 7-1 Grid-tied point control
Parameter Name
Active
Unlimited
power
Grid connection
with zero power
Issue 04 (2023-02-17)
-
Closed-loop controller
Limitation mode
Power adjustment
period
Power control
hysteresis
Active power output
limit for fail-safe
Copyright © Huawei Technologies Co., Ltd.
7 Man-Machine Interaction
Description
If this parameter is set to Unlimited,
the output power of the inverter is
not limited and the inverter can
connect to the power grid at the
rated power.
● If multiple inverters are cascaded,
set this parameter to SDongle.
● If there is only one inverter, set
this parameter to Inverter.
Total power indicates export
limitation of the total power at the
grid-tied point.
Specifies the shortest interval for a
single anti-backfeeding adjustment.
Specifies the dead zone for adjusting
the inverter output power. If the
power fluctuation is within the power
control hysteresis, the power is not
adjusted.
Specifies the derating value of the
inverter active power by percentage.
If the Smart Dongle does not detect
any meter data or the
communication between the Smart
Dongle and the inverter is
disconnected, the Smart Dongle
delivers the derating value of the
inverter active power by percentage.